Electric part-turn actuator SPR 0PA-M

Electric part-turn actuator SPR 0PA-M

Enclosure protection: IP 67, IP 68
Switching-off torque: 12 to 40 Nm
Operating time: 15 to 130 s/90°
Operating angle: 60 to 360 °
Weight: 1.4 to 2.4 kg
Ambient temperature: -25 to 55 °C
Flange size: F03, F04, F05, F07

Hi, my name is Marko. I will be glad to help you.

Ing. Marko Štofan

Standard equipment and functions with DMS3 control unit

  • Supply voltage:
    • 230 V / 50 Hz
  • Terminal board connection
  • 2 freely programmable relays R1, R2 (18 functions)
  • Relay READY
  • Safety function ESD (failure reaction)
  • Control by unified signal 0/4 - 20 mA, 4 - 12 mA, 12 - 20 mA, or 0/2 - 10 V (not for DMS3 in 2P version)
  • Control by permanent voltage (+24 V DC) - OPEN, CLOSE
  • Impulse control (inching duty) (+24 V DC) - OPEN, STOP, CLOSE
  • Timing mode / regime od operation
  • Electronic position transmitter 4 to 20 mA passive (not for DMS3 in 2P version)
  • Auxiliary voltage output 24 V DC, max. 40 mA for supply of the control inputs and transmitter
  • Output for failure messages
  • Space heater operated control unit
  • LED position indicator
  • Communication interface RS 232
  • Program for parameters setting by PC
  • Mechanical end stops
  • Mechanical connection ISO 5211 - flange size F03, F04, F05
  • Manual control
  • Enclosure protection IP 67

Additional equipment 

  • Supply voltage:
    • 220 V, 24 V / 50 Hz
    • 240 V, 120 V, 110 V, 24 V / 60 Hz
  • Communication cable DB-9F/RJ45
  • Mechanical connection ISO 5211 - flange size F07 - using a bracket
  • Mechanical connection - version with stand, lever and pull rods
  • Without mechanical end stops
  • Additional relays RE3, RE4, RE5 (not valid for Profibus and Modbus)
  • Additional relay module RE1, RE2, RE3, RE4, RE5 READY (not valid for Profibus and Modbus)
  • Version with control board PROFIBUS DP V0/V1 (only after agreement with the manufacturer)
  • Version with control borad MODBUS RTU (only after agreement with the manufacturer)
  • Enclosure protection IP 68

Similar products

Category products

Electric part-turn actuator SPR 0.1PA-M

Enclosure protection: IP 67, IP 68 Switching-off torque: 16 to 50 Nm Operating time: 10 to 160 s/90° Operating angle: 60 to 360 ° Weight: 3.2 to 5.2 kg
Enclosure protection: IP 67, IP 68 Switching-off torque: 16 to 50 Nm Operating time: 10 to 160 s/90°

Electric part-turn actuator SPR 0PA-M

Enclosure protection: IP 67, IP 68 Switching-off torque: 12 to 40 Nm Operating time: 15 to 130 s/90° Operating angle: 60 to 360 ° Weight: 1.4 to 2.4 kg
Enclosure protection: IP 67, IP 68 Switching-off torque: 12 to 40 Nm Operating time: 15 to 130 s/90°

Electric part-turn actuator UPR 1PA-M

Enclosure protection: IP 66, IP 68 Switching-off torque: 45 to 170 Nm Operating time: 5 to 80 s/90° Operating angle: 60 to 360 ° Weight: 14 to 15 kg
Enclosure protection: IP 66, IP 68 Switching-off torque: 45 to 170 Nm Operating time: 5 to 80 s/90°

Electric part-turn actuator UPR 2PA-M

Enclosure protection: IP 66, IP 68 Switching-off torque: 120 to 300 Nm Operating time: 5 to 80 s/90° Operating angle: 60 to 360 ° Weight: 20 to 24 kg
Enclosure protection: IP 66, IP 68 Switching-off torque: 120 to 300 Nm Operating time: 5 to 80 s/90°

Electric part-turn actuator UPR 2.4PA-M

Enclosure protection: IP 66, IP 68 Switching-off torque: 180 to 800 Nm Operating time: 20 to 160 s/90° Operating angle: 40 to 100 ° Weight: 29 to 33 kg
Enclosure protection: IP 66, IP 68 Switching-off torque: 180 to 800 Nm Operating time: 20 to 160 s/90°

Electric part-turn actuator UPR 2.5PA-M

Enclosure protection: IP 66, IP 68 Switching-off torque: 500 to 1200 Nm Operating time: 20 to 160 s/90° Operating angle: 40 to 100 ° Weight: 48 to 52 kg
Enclosure protection: IP 66, IP 68 Switching-off torque: 500 to 1200 Nm Operating time: 20 to 160 s/90°

Electric part-turn actuator SPR 1PA-M

Enclosure protection: IP 67, IP 68 Switching-off torque: 46 to 75 Nm Operating time: 10 to 80 s/90° Operating angle: 60 to 360 ° Weight: 6.5 to 34 kg
Enclosure protection: IP 67, IP 68 Switching-off torque: 46 to 75 Nm Operating time: 10 to 80 s/90°

Electric part-turn actuator SPR 2PA-M

Enclosure protection: IP 67, IP 68 Switching-off torque: 72 to 145 Nm Operating time: 5 to 80 s/90° Operating angle: 60 to 360 ° Weight: 12 to 14.5 kg
Enclosure protection: IP 67, IP 68 Switching-off torque: 72 to 145 Nm Operating time: 5 to 80 s/90°

Electric part-turn actuator SPR 2.3PA-M

Enclosure protection: IP 67, IP 68 Switching-off torque: 290 Nm Operating time: 20 to 160 s/90° Operating angle: 60 to 360 ° Weight: 6.5 to 34 kg
Enclosure protection: IP 67, IP 68 Switching-off torque: 290 Nm Operating time: 20 to 160 s/90°

Electric part-turn actuator SPR 2.4PA-M

Enclosure protection: IP 67, IP 68 Switching-off torque: 575 Nm Operating time: 40 to 160 s/90° Operating angle: 60 to 360 ° Weight: 20.5 to 21 kg
Enclosure protection: IP 67, IP 68 Switching-off torque: 575 Nm Operating time: 40 to 160 s/90°

An important fact of reliable operation is not only the correct design of fittings and servo drives, but also their subsequent care. With regular inspections and planned maintenance, you will prevent malfunctions and thus increase the reliability of the operation and extend its service life. For this purpose, the company REGADA also offers you comprehensive care of servo drives in your operation or just a selection from some of the listed services:

  1. Supervision during the first start-up of actuators in operation
  2. Connection and testing of actuators
  3. Connections and start-up of Rematic actuators - instruction
  4. Attaching the actuators to the valves and starting them
  5. Maintenance of actuators and periodic inspections
  6. Post-warranty repairs at the customer
  7. Post-warranty repair offer in Regada
  8. Training of service personnel
  9. Spare parts